Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM03667
Parcel: 12407179C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03667
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2003 JIM EGAN FIRE REVIEW Approved
07/23/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include funnel drain on fixture schedule and identify on riser diagram.
2. Provide water pressure calculations to verify water pipe sizing.
3. Clarify design of pan under water heater. 24" DEEP?
4. Include R.O. unit in fixture unit calculations.
07/23/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/23/2003 TACHONG1 WWM REVIEW Needs Review
07/23/2003 DAN CASTRO ZONING REVIEW Approved
07/23/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations. Reference Section 403.3, IMC 2000.
2. Modify smoke detector location for FC-13 to comply with Section 606.2.1, IMC 2000.
3. Clarify how the installation of the fan coils complies with 307.2.3, IMC 2000.
07/23/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Z_DO NOT USE
07/23/2003 ROBERT SHERRY WATER REVIEW Approved
07/23/2003 BLANCA ESPINO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2003 TAMI ACHONG OUT TO CUSTOMER Completed