Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM03667
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/23/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include funnel drain on fixture schedule and identify on riser diagram. 2. Provide water pressure calculations to verify water pipe sizing. 3. Clarify design of pan under water heater. 24" DEEP? 4. Include R.O. unit in fixture unit calculations. |
| 07/23/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/23/2003 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 07/23/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 07/23/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations. Reference Section 403.3, IMC 2000. 2. Modify smoke detector location for FC-13 to comply with Section 606.2.1, IMC 2000. 3. Clarify how the installation of the fan coils complies with 307.2.3, IMC 2000. |
| 07/23/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Z_DO NOT USE | |
| 07/23/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/23/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/23/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |