Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM03284
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/15/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/24/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/24/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/28/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 302.3, Uniform Administrative Code 1997. 2. Provide site drawing showing the size, route, and slope of the building drain. Reference Section 302.3, Uniform Administrative Code 1997. 3. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC 1994. 4. Modify the installation of the suspended water heater, located over 8'-0" above the finished floor, to comply with the access requirements of Section 511.0, UPC 1994 with AZ State amendments. 5. Modify the note on the water heater installation detail referring to the termination of the temperature and pressure relief line to exclude the mop basin; a mop basin is not an approved termination point. Reference Section 608.5, UPC 1994. 6. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 704.4, IECC 1998. 7. The cold water pipe sizes shown on detail 2/P-1.1 are undersized based on the your supplied calculations. At 5.33 PSI/100ft, a ½" pipe can handle only 2 fixture units and a ¾ pipe can handle only 8 fixture units. 8. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp) Reference Section 402.1, UPC 1994, as amended by the State of Arizona. |
| 07/28/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Receiving (room 106) is not classified as a storage area for the purposes of ventilation calculations; it is classified as "shipping and receiving", with a required ventilation rate of 0.15 CFM per square foot. Reference Table 403.3, IMC 2000. 2. Include the corridor, room 103, in the ventilation calculations. Reference Section 401.2, IMC 2000. 3. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2000. 4. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference Table 403.3, IMC 2000. 5. Smoke detectors shall be located upstream of any outside air connections. Reference Section 606.2.1, IMC 2000. 6. Provide auxiliary drain pans or secondary drain systems for fan coil units. Reference Section 307.2.3 IMC. 7. Provide return or relief air for rooms 106 and 103 (Receiving and Office). Reference Section 403.1, IMC 2000. 8. The energy code compliance reports indicate the town of Pima has been used as a basis for calculations; use Tucson. 9. Provide heating and cooling load calculations used to size the HVAC equipment. Reference Section 703.2, IECC 1998. |
| 07/28/2003 | Robert Sherry | WATER | REVIEW | Approved | |
| 08/06/2003 | Loren Makus | ENGINEERING | REVIEW | Denied | DATE: August 6, 2003 TO: Debbie Shinstine, PE SUBJECT: Family Dollar (Park and Drexel) Site Plan Review REVIEWER: Loren Makus ACTIVITY NUMBER: T03CM03284 SUMMARY: The Site Plan and Drainage Report were reviewed by Development Services Department, Engineering Division. The site plan was not approved at this time. The Drainage Report was accepted for site plan review purposes. Please address the following comments. Site Plan Comments: 1) Provide additional finish grades and spot elevations for the project site and the adjacent areas. Provide sufficient information to show that the proposed drainage will work and to show that off-site flows will be accepted. (City of Tucson Development Standards (DS) 2-02.2.1.A.23) 2) Show roof drainage patterns. Provide sidewalk scuppers at each downspout location and indicate that all flows up to a 10-year event will be conveyed under sidewalks. (DS 2-02.1.A.16 and DS 2-08.5.1.E) 3) Provide the basis of bearing. (DS 2-02.2.1A.5) 4) Provide basis of elevation. (DS 2-02.2.1A.5) 5) Correct the spelling in general notes 20 and 25. In note 20 change "STER" TO "DUMPSTER" and in note 25 change "MAINTENING" to "MAINTAINING." Revise the site plan to address all of these comments and resubmit two copies for review. Include copies of the drainage report and a letter explaining how each comment has been addressed. Loren Makus Senior Engineering Associate Engineering Division Development Services |
| 08/08/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Note on plans main exit doors to have sign, " This door To Remain Unlocked When Building Is Occupied." Please see section 1003.3.1.8 IBC for further clarification. 2. Provide accessible dimension for drinking fountain, (elevation). 3. Clear floor space for drinking fountain to be centered on unit. Reference section 602.2 ANSI A117.1 4. Submit a letter, for approval, to the Building Official, Dave Mann P.E.,for the deferred submittal of the metal building. Note: include approximate date of submittal. |
| 08/11/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 8/11/2003 Building plans may not be reviewed and approved until the site and landscape plans are approved and included in the submittal package. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/29/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 08/11/2003 | TAMI ACHONG | REJECT SHELF | Completed |