Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM02901
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Provide exhaust for clothes dryers. See Section 504, IMC 2000. |
| 01/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Based on the water calculations provided, the minimum branch size for a water closet (3 fixture units) is ¾", not ½". 2. Comment not addressed. Coordinate the waste riser diagram on sheet A-6 with the plumbing plan on the same sheet. "Typical each unit" is not appropriate with the configuration of the waste piping shown on the plumbing plan. 3. Revise the connection of the horizontal drainage lines to comply with Section 311.7, UPC 1994. 4. Coordinate the gas demand schedule with the water heater specified; it requires an input of 40,000 BTUH with natural gas. 5. Provide a detail for the Type B common vent for the water heaters showing the connectors, the connector rise (from the draft hood to the interconnection), and the height of the vent termination on the drawing. Reference Sections 502.12 (2), 512.2, and 517.0, UPC 1994. |
| 01/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/20/2004 | Blanca Espino | ENGINEERING | REVIEW | Denied | An approved Site Plan required. |
| 01/26/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 02/02/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/03/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs wastewater review of jt use or sewer easement. |
| 02/04/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/20/2004 | DAVID RIVERA | ZONING | REVIEW | Denied | Zoning will approve building plans upon final approval of the plans by all commnercial disciplines. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |