Permit Number: T03CM02753
Parcel: 124050590

Address:
749 N PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM02753
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/28/2003 GERRY KOZIOL WWM REVIEW Approved
07/28/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved 1. Access and clearance for backflow devices is required. Reference Section 603.2.3. Locating a backflow device above a ceiling will also require a fixed ladder for access to the platform.
2. A carbonator requires a reduced pressure backflow assembly, not a dual check valve with an atmospheric vent (Note H., Plumbing Notes, Sheet P-2). Refernce Section 603.3.12, UPC 1994.
07/28/2003 ROBERT SHERRY WATER REVIEW Approved
07/29/2003 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
07/29/2003 MONICA VALDEZ APPROVAL SHELF Completed