Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM02753
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/28/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
07/28/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
07/28/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. Access and clearance for backflow devices is required. Reference Section 603.2.3. Locating a backflow device above a ceiling will also require a fixed ladder for access to the platform. 2. A carbonator requires a reduced pressure backflow assembly, not a dual check valve with an atmospheric vent (Note H., Plumbing Notes, Sheet P-2). Refernce Section 603.3.12, UPC 1994. |
07/28/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/29/2003 | DAN CASTRO | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/29/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
07/29/2003 | MONICA VALDEZ | APPROVAL SHELF | Completed |