Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM02753
Parcel: 124050590

Address:
749 N PARK AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM02753
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/15/2003 JIM EGAN FIRE REVIEW Approved
07/15/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
07/21/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Water pressures greater than 80 PSI require a pressure reducer. Subsequent calculations are to be made using 80% of the reduced water pressure. Reference Section 608.2, UPC 1994.
2. Provide cleanout for hand sink in kitchen. Reference Section 707.4, UPC 1994 as amended by the State of Arizona.
3. Provide a flow control device for all fixtures directly connected to a grease trap. A floor sink may NOT be directly connected to a grease trap because the flow control device cannot be added to the tailpiece of the floor sink. Typically, two compartments of a 3-compartment sink are directly connected to a grease trap and one compartment is indirectly wasted to the floor sink. Reference section 1011.3, UPC 1994. Consult with the Pima County Health Department for their requirements (520-740-2760).
4. Access and clearance for backflow devices is required. Reference Section 603.2.3. Locating a backflow device above a ceiling will also require a fixed ladder for access to the platform.
5. A carbonator requires a reduced pressure backflow assembly, not a dual check valve with an atmospheric vent (Note H., Plumbing Notes, Sheet P-2). Refernce Section 603.3.12, UPC 1994.
07/21/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/28/2003 TACHONG1 WWM REVIEW Needs Review
07/28/2003 TACHONG1 ZONING REVIEW Needs Review
07/28/2003 TACHONG1 MECHANICAL-COMMERCIAL REVIEW Needs Review
07/28/2003 TACHONG1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2003 TAMI ACHONG OUT TO CUSTOMER Completed