Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM02534
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM02534 DENIED 12/17/03 1. Registrant shall sign and seal drawings. 2. Phase B on Panel A is overloaded. Total VA comes to 25,053; total amps 209, which exceeds the 200A capacity of the panel. 3. Phase B of Panel B is overloaded. Total VA of 6150 equals 51.3 amps, which exceeds the 50A capacity of the panel, and the 50A ampacity of the conductor. 4. Panel B is called out as 50A on the panel schedule and 60A on the line diagram. Please clarify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2003 | MONICA VALDEZ | APPROVAL SHELF | Completed |
| 12/18/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |