| 12/18/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM02534 DENIED 12/17/03 1. Registrant shall sign and seal drawings. 2. Phase B on Panel A is overloaded. Total VA comes to 25,053; total amps 209, which exceeds the 200A capacity of the panel. 3. Phase B of Panel B is overloaded. Total VA of 6150 equals 51.3 amps, which exceeds the 50A capacity of the panel, and the 50A ampacity of the conductor. 4. Panel B is called out as 50A on the panel schedule and 60A on the line diagram. Please clarify. |