Permit Number: T03CM02534
Parcel: 141148180

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM02534
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2003 JIM EGAN FIRE REVIEW Approved
06/10/2003 GERRY KOZIOL WWM REVIEW Approved
06/16/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC.
2. Provide a Type II hood over all commercial food heat-producing appliances. Reference Section 507.2, IMC 2000.
06/16/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide indirect waste for prep sink. Reference Section 801.2, UPC 1994.
2. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC. Include all existing fixtures in the shell building when calculating the total demand and determining pipe sizes
3. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
4. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994.
5. Floor sinks and floor drains can't be connected to a grease trap. Reference Section 1011.3, UPC 1994.
06/16/2003 ROBERT SHERRY WATER REVIEW Approved
06/25/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. A 12" maneuvering clearance is required at the women's restroom door. Reference section 404.2.4 ANSI 117.1. Revise plans
2. The fire rated wall specified calls for fire retardant wood and furring channels. Provide detail and specifications per Table 719.1 IBC
3. Provide the through penetration fire-stop system to be used for the fire rated wall penetrations. Reference section 711.4.1.2 IBC
4. Provide a structural analysis for the proposed soffit and glulam beam. Include method of attachment to existing trusses in calculations.
07/03/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
07/09/2003 MONICA VALDEZ REJECT SHELF Completed