Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02450
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A-1
1. No listing number or IBC item number from Table 719.1.(2) was provided. The detail appears similar to UL design U425. Please clarify.

2. Separate facilities are required for each sex. Ref. IBC 2902.2.

3. Please show the required drinking fountain or note that a bottled water dispenser will be provided in an accessible location and be on site for the final inspection. Ref. IBC 2902.1.

Sheet A-4
1. The single light trench door requires safety glazing. Please specify. Ref. IBC 2406.2.

Sheet A-6
1. The counter height in the common use break room must be 28" to 34" maximum above the finished floor. Ref. ANSI A117.1, 902.3.

Sheet A-7
1. Please specify water closet flush control on transfer side. Ref. ANSI A117.1, 604.

PLUMBING COMMENTS
Sheet P-1
1. The venting for toilet room 123 appears to be undersized. Ref. UPC Table 7-5.

2. Please specify water heater mounting height and access / working space provisions. Ref. UPC 511.

3. Specify cross connection control for the hose bibb. Ref. UPC 603.

MECHANICAL COMMENTS
Sheet M-1
1. Coordinate with electrical comment 1.

ELECTRICAL COMMENTS
Sheet E-1
1. Please show the smoke detectors in the return ducts. Coordinate with mechanical. Ref. IMC 606.
06/17/2003 EROSE1 ENGINEERING REVIEW Needs Review
06/17/2003 EROSE1 WWM REVIEW Needs Review
06/17/2003 ELAINE ROSE ZONING REVIEW Needs Review
06/17/2003 EROSE1 FIRE REVIEW Needs Review
06/17/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2003 ELAINE ROSE OUT TO CUSTOMER Completed