Permit Number: T03CM01875
Parcel: 123030590

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM01875
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Resize vent for P-3 and P-2 to comply with Table 7-4 Footnote 3, UPC 1994.
2. Provide vent piping of sufficient size to comply with Section 904.1, UPC.
3. Show size of scuppers on the drawing. (only the height of the scupper is shown on detail 4/A2.4BN). Reference Appendix D, UPC. Note: no provisions for overflows for the roof are evident on the plans.
10/01/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/17/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. MPR does not reflect the required fixtures per Table 2902.1 IBC. Note: A total fixture count and occupant load of the school may be used if the total is in compliance with Table 2902.1 IBC. Note: May not use TUSD Enrollment numbers. Utilize Table 1003.2.2.2 IBC
10/21/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
10/21/2003
Comments from previous review have not been addressed. Please contact Patricia at 791-5608 ext 1179 for additional information prior to resubmittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2003 TAMI ACHONG OUT TO CUSTOMER Completed
12/05/2003 ANGIE SHOFFSTALL REJECT SHELF Completed