| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Resize vent for P-3 and P-2 to comply with Table 7-4 Footnote 3, UPC 1994. 2. Provide vent piping of sufficient size to comply with Section 904.1, UPC. 3. Show size of scuppers on the drawing. (only the height of the scupper is shown on detail 4/A2.4BN). Reference Appendix D, UPC. Note: no provisions for overflows for the roof are evident on the plans. |
| 10/01/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/17/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. MPR does not reflect the required fixtures per Table 2902.1 IBC. Note: A total fixture count and occupant load of the school may be used if the total is in compliance with Table 2902.1 IBC. Note: May not use TUSD Enrollment numbers. Utilize Table 1003.2.2.2 IBC |
| 10/21/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 10/21/2003 Comments from previous review have not been addressed. Please contact Patricia at 791-5608 ext 1179 for additional information prior to resubmittal. |