Permit Number: T03CM01875
Parcel: 123030590

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM01875
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2003 JIM EGAN FIRE REVIEW Approved
05/09/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct scale of plumbing site plan, 1/P1.0BN. Reference Section 302.3, Uniform Administrative Code, 1994.
2. Resize the RPBP and the water meter to comply to Section 610.2, UPC 1994.
3. Correct installation of P-2 and P-3 to conform to Section 908.1, UPC, 1994.
4. Termination of the excess pressure relief from the water heater over a mop sink is not approved location. Reference Section 608.5, UPC, 1994.
5. Provide vent piping of sufficient size to comply with Section 904.1, UPC.
6. Provide calculations and sizes of scuppers and downspouts. Reference Appendix D, UPC.
05/09/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the exhaust volume scheduled for EF-3 with the exhaust volumes shown on the floor plan.
05/09/2003 ROBERT SHERRY WATER REVIEW Approved
05/20/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
5/20/2003
A yellow card and site plan are required for handi-cap review and approval prior to building plan approval.
All new structures and parking must be ADA compliant.
05/28/2003 GERRY KOZIOL WWM REVIEW Approved
06/03/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. MPR does not reflect the required fixtures per Table 2902.1 IBC. Note: A total fixture count and occupant load of the school may be used if the total is in compliance with Table 2902.1 IBC.
2. Provide occupant loads on the plans for the MPR building. Note, a 7 net ratio is to be used for the assembly area. Reference Table 1003.2.2.2 IBC
3. The urinal is to be accessible per section 1108.2 IBC
4. Weep screed is not shown on plans for the stucco system. Reference section 2512.1.2 IBC. Revise plans
5. Overflow for the roof leader appears to be undersized. Provide calculations for sizing of overflow.
6. Ceiling Plan shows lay-in tile and bathroom cross-section indicates drywall. Please clarify. Note attic ventilation required if drywall.
06/05/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/05/2003 DOUG WILLIAMS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
06/06/2003 ANGIE SHOFFSTALL REJECT SHELF Completed