Permit Number: T03CM01865
Parcel: 12213143C

Review Status: Completed

Review Details: REVISION - SITE

Permit Number - T03CM01865
Review Name: REVISION - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2006 ANDREW CONNOR LANDSCAPE REVIEW Denied 1) Any change in design or land use requires a new review and approval process for the landscape plan. Certificates of Occupancy will not be issued, nor will the building be occupied, until the landscaping on the site meets the approved landscape plan criteria The site plan and landscape plan must show identical site layout to avoid conflict between the two plans per DS 2-07.2.0. Submit revised landscape plan to continue review.
01/10/2006 ANDREW CONNOR NPPO REVIEW Passed
01/23/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: January 23, 2006
ACTIVITY NUMBER: T03CM01865-R
PROJECT NAME: Benzinger Apartments
PROJECT ADDRESS: 4225 E. Fort Lowell Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN


1. A parking area access lane is required to be a width of 24' per Tucson Land Use Code 3.3.7.2. The proposed width requires a variance through the Broad of Adjustments. Please seeing the Zoning Section's comments regarding the reduction in PAAL width.

2. Be advised Handicap curb access ramps are required to be constructed with truncated domes, per recent a Federal ADA requirement. Show a detail or add a general note to the site plan indicating all public and private handicap curb access ramps will have truncated domes.
01/28/2006 MICHAEL ST. PAUL ZONING HC SITE REVIEW Approved
01/28/2006 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

FROM: Michael St.Paul
Planner Technician

PROJECT:
T03CM01865 (revision)
4225 East Fairmont Street
Apartment complex
TRANSMITTAL:
January 28, 2006

COMMENTS: The follow comments are for the purpose of applying for a variance before the Board of Adjustment.


The minimum width for a two-way parking area access land (PAAL) is twenty-four feet (24'-0"). (Please see LUC Section 3.3.7.2 and Development Standards 3-05 Table 1.) Twenty-one (21'-0") has been provided. The minimum distance from a PAAL and a screen wall is two feet (2'-0"). Please see DS 3-05.2.2.B.3.) Less than two feet has been provided.
12/29/2005 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2006 GBONILL1 OUT TO CUSTOMER Completed
05/31/2006 SUE REEVES REJECT SHELF Completed