Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM01542
Parcel: 140430130

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM01542
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q Detail 25 on Sheet A7.02 indicates a tube steel section at the drip edge of the new canopy. The structural drawings use instead a wide flange section for this member. Which is it to be? Please clarify.

STRUCTURAL:

q Detail 266 on the new Sheet S1, which indicates a new exterior steel deck canopy, shows an existing canopy floating over a wide flange beam that is to be connected to an existing wall. Where is the new deck that should be mounted to the new wide flange beam? Further, I could not find in any of the drawing packages a reference to this steel deck which floats above the wide flange beam. Please clarify.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed