Permit Number: T03CM01511
Parcel: 10824012A

Address:
2484 E RIVER RD

Review Status: Completed

Review Details: SITE

Permit Number - T03CM01511
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2003 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Engineering scale is required for all plans submitted to the City of Tucson for review. D.S. 2-02.2.1.A.1

2. Indicate property description. D.S. 2-02.2.1.A.2

3. Indicate project and or administrative address. D.S. 2-02.2.1.A.3

4. Indicate all existing and proposed buildings and structures, overhangs, roof slope and downspouts. D.S. 2-02.2.1.A.6

5. Indicate drainage patterns and finish grades. D.S. 2-02.2.1.A.16

6. Indicate refuse container location, size and access thereto fully dimensioned. D.S. 2-02.2.1.A.32

7. Correct and revise "Existing Parking" and "Existing Drive" to read "Proposed Parking" and "Proposed Drive".
04/10/2003 BLANCA ESPINO SANITATION REVIEW Denied SEE ENGINEERING FOLDER FOR COMMENTS.
04/11/2003 JIM EGAN FIRE REVIEW Denied Fire sprinklers refquired for structures in this development per approved COT Water Plan. Provide fire sprinkler system design criteria on plans.
04/20/2003 DAN CASTRO HANDICAP-SITE REVIEW Passed
04/20/2003 DAN CASTRO ZONING REVIEW Denied 1. Note the project address on the site plan.

2. Review of this plan by the Zoning Review Section may be done over the counter. Please contact Dan Castro at 791-5608 ext. 1180 to set an appointment.
04/24/2003 JOE LINVILLE NPPO REVIEW Denied Submit a copy of the approved Development Plan NPPO/Landscape Plans.
04/24/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Site landscaping must conform to City Of Tucson regulations in addition to Hacienda Del Sol restrictions. Any proposed landscaping is subject to review. LUC 3.7

2) Revise the plans the plans as requested by other agencies and submit a landscape plan for review, if applicable. If no landscaping is proposed at this time, the areas of the lot that are not developed must be treated with an inorganic dust control material. LUC 3.7.2.7

3) Add the following note to the site plan. Any proposed landscaping must be approved by the City of Tucson Development Services Department.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
04/24/2003 ANGIE SHOFFSTALL REJECT SHELF Completed