Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM00139
Parcel: 128010010

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM00139
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2003 DAVID RIVERA ZONING REVIEW Approved
01/13/2003 DAVID RIVERA NPPO REVIEW Passed
01/13/2003 JAMES TATE FLOODPLAIN REVIEW Approved
01/14/2003 JIM EGAN FIRE REVIEW Approved
01/24/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:
1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications and the 1994 UPC with State of Arizona amendments. Any revisions to this plan will require an additional review and approval by Willdan.

ARCHITECTURAL COMMENTS:
No comment.

STRUCTURAL COMMENTS:
Sheet S0.0

1. Please provide City of Tucson required special inspection documents (see attachment).

PLUMBING COMMENTS:
No comment.

MECHANICAL COMMENTS:
Sheet M1.0

1. The outside air component is identified at 500 cfm. However, IMC Section 403.2 requires 0.3 cfm/s.f. of retail street level floor space and 0.15 cfm/s.f. for storage rooms, etc. Please review and clarify compliance. Reference IMC Section 403.2.
ELECTRICAL COMMENTS:
See energy comments below.

ENERGY CODE COMMENTS:
Sheet E1.0

1. The connected lighting load is listed at 26,036 watts. The tenant floor area is listed at 4232 square feet. The resultant lighting load in watts per square foot is 6.15. The IECC allowable retail store lighting load is 3.1 watts per square foot. Please review and correct. Reference IECC Section 705.4.

Sheet E2.0
1. Interior lighting controls shall allow the occupant to uniformly reduce the connected lighting load by at least 50%. Please review and clarify compliance. Reference IECC Section 705.2.1.

Sheet M2.0
1. Please clarify HVAC ducts shall be sealed with welds, gaskets, mastics, and mastic-plus-embedded-fabric systems or tapes. Tapes and mastics shall be listed and labeled in accordance with UL181A and UL181B. Duct tape is not permitted as a sealant on any ducts. Reference IECC Section 503.3.3.4.

ACCESSIBILITY COMMENTS:
No comment.
03/14/2003 EROSE1 WATER REVIEW Needs Review
03/14/2003 EROSE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2003 ELAINE ROSE OUT TO CUSTOMER Completed