Permit Number: T03BU03181
Parcel: 13816024A

Address:
335 E ELVIRA RD

Review Status: Completed

Review Details: GRADING

Permit Number - T03BU03181
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Grading Permit review - 335 E. Elvira
REVIEWER: Doug Williams
DATE: 15 January 2004
ACTIVITY NUMBER: T03BU03181/T03OT02275

SUMMARY: Engineering Division has reviewed the subject grading permit application received 22 DEC 2003. Approval is not recommended at this time. Please address the following comments prior to resubmittal:

1. Please indicate on the plan that the submittal is a grading plan in addition to a site plan, or submit a separate grading document.
2. Depict and label grading limits on the plan.
3. Provide general grading notes.
4. Grading shall conform to the 2000 International Building Code (IBC) local amendment. Please provide a note indicating such on the plan. For additional grading permit and plan information, go to http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf
5. The plan depicts a fill area south of the basin, yet the grading permit application and cut/fill quantities provided indicate a zero fill quantity - revise as necessary.
6. The plan does not demonstrate that 100-year water surface elevation (41.07) will be contained within the basin or property limits. Depict the 100-year ponding limits on the plan and provide sufficient elevation information demonstrating containment onsite.
7. Provide a north-south cross section for the basin, including depiction of the berm, fully dimensioned and labeled with elevations provided.

Please submit three (3) sets of the grading plan with the next submittal.

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
01/20/2004 ACONNOR1 NPPO REVIEW Denied Need to submit an approved site plan including Stormwater and Native Plant Preservation regulations.

1) All site plans shall inclued Landscape plans for rentention/detention areas.
DS 10-01.4.3.2 Stormwater Detention/Retention Manual. 4.3.2 Basin Landscaping.

2) Site Plans shall include a Native Plant Preservation Plan
Development Standard 10-01.4.3.2
DS 2-15.3.0 Native Plant Preservation Plan Submittal
LUC 3.8.4.2 Native Plant Preservation.
01/21/2004 Peter McLaughlin ZONING REVIEW Denied Engineering approval required prior to Zoning approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2004 LISA LESNY OUT TO CUSTOMER Completed