Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03BU01081
Parcel: 140430130

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03BU01081
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q What is the width of the concrete columns?

STRUCTURAL:

q How do the three 6x6x1/4 beams attach to one another at their convergence at the northern canopy? This previous comment has not been addressed. The response indicates to see Detail 265, however Detail 265 has not been presented (nor could a key be found on the framing plan to Detail 265).

q Are there footings for the concrete columns? Any steel in these concrete columns? Calculations for the columns? Please provide. This previous comment has not been addressed. As a response it was suggested that the footings and columns for these canopies were reviewed under earlier submittals, however the plans within the approved "foundation only" permit specifically excluded the canopy columns and footings (the note reads "Not Part of This Permit" and no further information is provided). Please provide.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-
05/27/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2003 ELAINE ROSE OUT TO CUSTOMER Completed