Review Details: PLUMBING
Permit Number - T02PL01860
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water demand and pipe sizing calculations for the laundry facility. Reference Section 610, UPC 1994. 2. The plans still reflect several encroachments into the public right of way, including construction of the water line. Please clarify. Note: A plumbing permit cannot be issued for work in the right of way. 3. Provide detail on drawing of how the backflow preventers are to be protected from mechanical damage by vehicles or other causes. Reference Section E21, UPC 1994. |
| 04/08/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 4/8/03 Comments from last review have not been addressed. |