Permit Number: T02PL01860
Parcel: 13811089A

Review Status: Completed

Review Details: PLUMBING

Permit Number - T02PL01860
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water demand and pipe sizing calculations for the laundry facility. Reference Section 610, UPC 1994.
2. The plans still reflect several encroachments into the public right of way, including construction of the water line. Please clarify. Note: A plumbing permit cannot be issued for work in the right of way.
3. Provide detail on drawing of how the backflow preventers are to be protected from mechanical damage by vehicles or other causes. Reference Section E21, UPC 1994.
04/08/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
4/8/03
Comments from last review have not been addressed.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
04/08/2003 ANGIE SHOFFSTALL REJECT SHELF Completed