Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T02PL01860
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2003 | MARTIN HAEBERLE | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Plans reflect several encroachments into the public right of way, including construction of the water line. Please clarify. note: A plumbing permit cannot be issued for work in the right of way. 2. Indicate on plan documents that a separate water shut off shall be provided at each MH lot. Reference Appendix E 18 UPC. 3. Provide a pressure relief valve at back flow preventers per Appendix E 20. 4. Back flow preventers are located in the alley. How is protection of the devices being provided? Reference Appendix E 21. 5. Indicate on plans required flex connector required to MHs. Reference Appendix E 22. |
| 01/06/2003 | DAN CASTRO | ZONING | REVIEW | Denied | Zoning 01/03/03 Please provided copies of the stamped approved site plan with the resubmittal of these plans. This is required prior to review and approval. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/28/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |