Review Details: PLUMBING

Permit Number - T02PL01860
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2003 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Denied 1. Plans reflect several encroachments into the public right of way, including construction of the water line. Please clarify. note: A plumbing permit cannot be issued for work in the right of way.
2. Indicate on plan documents that a separate water shut off shall be provided at each MH lot. Reference Appendix E 18 UPC.
3. Provide a pressure relief valve at back flow preventers per Appendix E 20.
4. Back flow preventers are located in the alley. How is protection of the devices being provided? Reference Appendix E 21.
5. Indicate on plans required flex connector required to MHs. Reference Appendix E 22.
01/06/2003 DAN CASTRO ZONING REVIEW Denied Zoning
01/03/03
Please provided copies of the stamped approved site plan with the resubmittal of these plans. This is required prior to review and approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2003 DELMA ROBEY OUT TO CUSTOMER Completed