Review Details: FLOODPLAIN

Permit Number - T02OT01939
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/26/2002 ELIZABETH EBERBACH FLOODPLAIN REVIEW Denied SUBJECT: 22nd/Swan Parking Lot Engineering Review
REVIEWER: Elizabeth Eberbach
DATE: December 26, 2002
ACTIVITY NUMBER: T02OT01939

SUMMARY: The Site Plan, Drainage Report, and Floodplain Use Permit application were received by Engineering on December 23, 2002. The Engineering Section of Development Services has reviewed the received items and does not recommend approval for the Floodplain Use Permit application for this project. The Drainage Report was reviewed for Grading Plan purposes only.

FLOODPLAIN USE PERMIT APPLICATION COMMENT
1) Clearly label the minimum finished grade elevation / minimum finished floor elevations for NAVD'88 and NGVD'29 on Site/Grading Plan.

The next submittal should address all comments. Submit revised Site/Grading Plan. If you have any questions, you may call me at 791-5550 extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Section
Development Services