Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM05567
Parcel: 137070570

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM05567
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Provide the enercalc`s specified on sheet 3 of calc`s.
2) Specify ! What are the rectangles(20x8) shown on sheet A1.1?
3) Comply to section 501.2 of the 2000 IBC "premises identification" as
Specified in the Pima county address display requirements.PH 740-6480
01/31/2003 RSHERRY1 PLUMBING-COMMERCIAL REVIEW Denied 1. Resubmit the water calculations using the total fixture units. Reference Section A3, UPC.
2. Condensate drains that terminate at or above grade outside the building must terminate in an area that is capable of absorbing the condensate flow without surface drainage. Reference local amendments to Section 307.2.1, IMC.
3. Provide access and working space for WH-1. Reference Section 511.0 UPC.
4. Provide ½" CW from trap primer to P-5 (Instead of P-2) on waste and vent isometric 3, sheet P2.1.
5. Indicate location of trap primer valves on HW & CW isometrics, sheet P2.2.
6. Provide CW shut off valves for each building entrance. Reference Section 605.3, UPC.
7. Correct total connected load for gas meter #3.
8. Indicate location of WH-4 on plans.
9. Indicate location of supply and drain piping for EC-1 on plans and isometrics.
10. Show fixture and flow control device connected to GT-1 on waste and vent isometric (detail 2, sheet P2.1). Reference Section 1011.0, UPC.
11. Provide location and sizing information for gutters and downspouts. Reference Appendix D, UPC.
01/31/2003 RSHERRY1 MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide approved combination fire/smoke dampers for protection of ducts and penetrations of fire resistive walls. Reference Section 715, IBC.
2. Provide listing information for fire dampers being applied to door grilles in Kiln Room. Reference Section 715.3, IBC.
3. Provide calculations showing the maximum exposed surface temperature of the kiln exhaust duct will not exceed 120°F. Reference Section 604.2, IMC.
4. Provide service space for roof mounted equipment. Reference Section 306.6 IMC.
5. Provide auxiliary drain pans or secondary drain systems for fan coil units. Reference Section 307.2.3 IMC.
01/31/2003 MARTIN HAEBERLE WATER REVIEW Approved
02/07/2003 GERRY KOZIOL WWM REVIEW Approved
02/10/2003 JIM EGAN FIRE REVIEW Approved
02/10/2003 BLANCA ESPINO FLOODPLAIN REVIEW Denied Site Plan
1. Indicate the water surface elevation of the detention/retention basin. D.S. 2-02.2.1.15

2. Indicate all existing and proposed impervious coverage for buildings, sidewalks and PAALs. Sheet A0.1 indicates existing and proposed square footage area, which does not coincide with the Hydrology Report. Correct and revise.

3. FYI - It looks like the collection vehicle will jump the curb as is it backs away from the refuse container. The redline indicated on Sheet C1.1 will give the collection enough maneuverability to backup and exit the site freely.

Hydrology Report
1. Submit a routing table and perform the routing for existing and proposed 2-, 5-, 10-, and 100-year flood peaks.

2. Indicate the water surface elevation of the detention/retention basin.

3. Indicate all existing and proposed impervious coverage for buildings, sidewalks and PAALs. Sheet A0.1 indicates existing and proposed square footage area, which does not coincide with the Hydrology Report. Correct and revise.

4. Indicate the 5- and 100-year runoff coefficients used for soil types B and D as per the Stormwater Detention/Retention Manual Table 3.4
12/03/2002 PETER MCLAUGHLIN ZONING REVIEW Passed
12/31/2002 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

Sheet E6
1. AC-1 through AC-18 are listed on Sheet M2.0 as having MOCP 35 A. Yet the CB's at the panels are 40 A. And one, AC-17, is protected by NPC-1,3,5 at 60 A. Please correct/explain.
2. Roof mounted receptacles are fed by NPC-33 on HVAC Power Plan. On Panel Schedule, this circuit feeds lighting. Roof mounted receptacles are on NPC-26. Please correct.
3. Outdoor units CU-1 through CU-3 are listed on Sheet M2.0 as having MOCP 15 A. Yet the CB's at the panels are 20 A. Please correct/explain.
4. CU-1 are fed by NPE-40 on HVAC Power Plan. NPE-40 is listed as a spare on the Panelboard Schedule. However, CU-1 does appear on NPE1, Circuits 7,9. Please correct.
5. FC-1 and FC-2, at 6.8 MCA, are fed by NPE on HVAC Power Plan. Yet they are not on the Panelboard Schedule for that panel. It appears the intent was to feed them from Panel NPE1. Please correct.
6. FC-1, at 44 watts, is fed by NPE-40,42 on HVAC Power Plan. Yet those circuits are listed as spare on the Panelboard Schedule, and no feed for FC-1 on NPE. The intent may have been to power this FC-1 from NPE1. Please clarify. There are three FC-1s listed on NPE1, all at 708 VA per phase.

Sheet E9
1. The "B" phase on Panel NPC appears overloaded. Some of the branch circuits appear to be carrying higher volt-amperes than are listed on the Schedule. Please double check/correct as necessary.

Sheet E10
1. Feeders for Panels CPC and CPE, serve primarily nonlinear loads, thus the neutrals would have to be considered as current-carrying per 301-15 (b) (4) (c). Thus the 3/0 conductors would not be protected by the 200 A CBs.
2. No equipment ground shall be installed in conduit with service entrance conductors.
3. Could you please clarify what is meant by "service ground", from the panels in the buildings remote from the service entrance.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2003 LISA LESNY OUT TO CUSTOMER Completed