Permit Number: T02CM05314
Parcel: 13316013B

Address:
6500 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05314
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/19/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Completed Sheet E1
1. Indicate on plans that optional loads will be automatically shed if actual demand exceeds generator rating, if such is the case per the response letter of January 10, 2003.
2. Indicate on plans the information contained in Item 2 for sheet E1 in your response letter of January 10, 2003.

Sheets E3, E11, E13, E15
1. Your response letter indicates the relocation/reuse of UL listed and labeled connectors. Please put this information on the plans.

Sheet E6
1. Your response letter indicates that the RTU's disconnects come integral with the equipment. Per a conversation of February 21, 2003, the disconnects also come integral with the equipment. Please put this information on the plans.

Sheet E8B
1. Provide weight and mounting detail for transformer T-6. This may have to go for structural review.
02/24/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
02/28/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Sheet E1
1. Indicate on plans that optional loads will be automatically shed if actual demand exceeds generator rating, if such is the case per the response letter of January 10, 2003.
2. Indicate on plans the information contained in Item 2 for sheet E1 in your response letter of January 10, 2003.

Sheets E3, E11, E13, E15
1. Your response letter indicates the relocation/reuse of UL listed and labeled connectors. Please put this information on the plans.

Sheet E6
1. Your response letter indicates that the RTU's disconnects come integral with the equipment. Per a conversation of February 21, 2003, the disconnects also come integral with the equipment. Please put this information on the plans.

Sheet E8B
1. Provide weight and mounting detail for transformer T-6. This may have to go for structural review.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2003 LISA LESNY OUT TO CUSTOMER Completed