Permit Number: T02CM05302
Parcel: 124160710

Address:
700 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05302
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2003 JIM EGAN FIRE REVIEW Approved
02/05/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/20/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Denied see below:







SUBJECT: Borton School Activity Center
REVIEWER: Doug Williams
DATE: 20 Feb 03
ACTIVITY NUMBER: T02CM05302

SUMMARY: Engineering Division has reviewed the Drainage Report received on 12 February 2003. Approval is not recommended at this time. The following comments are offered:


1. Depict the limits of the 100-year floodplain affecting the site, with water surface elevations (wsel's) on a plan with a scale no smaller than 1" = 40'. Provide appropriate recommendations for floodplain use permit and finished floor elevation certification requirements, in accordance with sections 2.3.1.4 C (1, 2 & 6) and 5.2 (5 & 6) of the City of Tucson Standards Manual for Drainage Design and Floodplain Management (SMDDFM) - Development Standard 10-02.0.

2. The hydraulic cross section location should be depicted on a map of similar, suitable scale, in accordance with section 2.3.1.4 e - SMDDFM.

3. Depict the limits of the 100-year floodplain on the site plan as it affects this project (see comment # 1) Development Standard 2-02.2.1(15).

4. Depict drainage patterns, finished grades or topographic contours and recommended finished pad and floor elevations on the site plan, per Development Standard 2-02.2.1(16).
5. A floodplain use permit will be required for this project. Please complete a floodplain use permit application and include with the resubmittal. A $50.00 floodplain use permit fee will be charged.

6. A resubmittal fee of $150.00 is required for the drainage report review, in accordance with Tucson Code, Section 26-11.2(i).

If you have any questions, I can be reached at 791-5100 ext. 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Senior Engineering Associate
Engineering Section
Development Services Department
02/24/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2003 LISA LESNY OUT TO CUSTOMER Completed