Permit Number: T02CM05302
Parcel: 124160710

Address:
700 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM05302
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2002 JIM EGAN FIRE REVIEW Denied 1. PROVIDE COMPLETE CODE REVIEW CHECKLIST FOR NEW AND EXISTING BUILDING.
2. OCCUPANT LOAD SHOULD BE BASED ON CONCENTRATED USE. (1:7)
3. FIRE SPRINKLERS REQUIRED FOR A-3 OCCUPANCIES WITH AN OCCUPANT LOAD OF 300 OR MORE.
SHOW LOCATION OF EXISTING FIRE HYDRANTS ON PLAN.
12/05/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied ....T02CM05302....700 E. 22ND ST. .....DGL...12/05/02 ....... ...1. PROVIDE COMPLETED " CODE REVIEW CHECKLIST". ...2. CLARIFY OCCUPANT LOAD 1/7 SF , OL =~335 +, REVISE DRAWINGS. ....................................................... ...3. ADDRESS FIRE COMMENTS. ................................... ...4. PROVIDE SEPARATION FOR STORAGE PER TABLE 302.1.1, IBC PG #23, REF DWG #15-A2.1, ONE HOUR SEPARATION. .................................................................. ...5. FULLY DETAIL REQUIRED FIRE SEPARATIONS, PER #4 ABOVE AND PROVIDE COPY OF THE LISTING ON DRAWINGS. .................................................................... ...6. SHOW PREMISES IDENTIFICATION ON SITE PLAN, REF DWG #15-A1.1, PER IBC SEC 501. ............................ ...7. SHOW ADDRESSING PER PIMA COUNTY ADDRESSING ORDINANCE, SEE ATTACHMENT, REF DWG #15-A1.1. ........................................................................ ...8. PROVIDE ALLOWABLE AREA CALCULATION FOR SITE, PER IBC SEC 5, REF DWG #10G1.1. ........................ ...9. CLARIFY EXTERIOR WALL FIRE-RESISTANCE RATING REQUIREMENTS PER IBC CHAP 6, REF DWGS #15-A1.1 AND #10-G1.1, EXPLAIN, DETAIL AND PROVIDE COPY OF LISTING ON DRAWINGS. .................................................. ..10. CLARIFY AUTOMATIC FIRE SPRINKLER REQUIREMENTS PER FIRE COMMENTS AND IBC SEC 903.2.2. ........................................................................... ..11. SHOW LOCATION AND DETAIL OF SIGN POSTED INDICATING OCCUPANT LOAD PER IBC SEC #1003.2.2.5.... ..12. PROVIDE ADEQUATE GRADE ELEVATIONS ON DRAWINGS TO SHOW CONFORMANCE WITH IBC SEC #1003.2.7, AND SEC #1104. .............................................. ..13. SHOW ACCESSIBILE MEANS OF EGRESS PER IBC SEC #1003.2.13, AND ACCESSIBILE ROUTE PER SEC #1104. ............................................................................. ..14. CLARIFY ACCESSIBILITY, PER IBC SEC 1108, OF OTHER FEATURES AND FACILITIES ( TOILETS, DRINKING FOUNTAINS, etc. ). .......................................................... ..15. FULLY DETAIL MECHANICAL SCREEN ( 1/15-A4.1 ), INCLUDING CONNECTIONS OF TUBES TO EACH OTHER, EXPANDED METAL TO TUBES AND TUBES TO STUD WALL. ............................................................................. ..16. SHOW MINIMUM PLUMBING FIXTURES ON DRAWINGS FOR COMPLIANCE WITH IBC SEC 29. .............. ..17. CLARIFY SHEAR TRANSFER AT WALL BETWEEN DIAPHRAGMS I & II, REF STRUC CALCS PG 13/14, DWG 15-S1.1 & 15-S3.1. ............................................................ ..18. PROVIDE DETAILS FOR INSTALLATIONS OF HOLD-DOWNS INCLUDING FASTENING TO METAL STUDS. ..19. PROVIDE ARCHITECTURAL DETAILS FOR NEW STAIR INTO EXISTING , PER IBC CHAP 10 , INCLUDING HANDRAILS. .................................................................... ..20. PROVIDE TWO SETS OF SHOP DRAWINGS AND CALCULATIONS FOR TRUSSES. ........................................ ..21. PROVIDE INSPECTION PROGRAM PER 1994 U.A.C. SEC 302.5. ....................................................................... ..22. SPECIAL INSPECTION REQUIRED FOR :.................... ............1. FILED WELDING .............................................. .............2. FOUNDATION EXCAVATION AND COMPACTION. ..23. PROVIDE 2ND SET OF SPECIFICATIONS FOR FIELD SET OF APPROVED PLANS. .. .
12/13/2002 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/24/2002 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Approved
12/24/2002 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide fire dampers at penetrations of required fire barrier separation of storage room. References section 302.1.1 IBC.
12/24/2002 MARTIN HAEBERLE WATER REVIEW Approved
12/26/2002 MSTPAUL1 FLOODPLAIN REVIEW Needs Review Client has comments.
12/26/2002 DAVID RIVERA ZONING REVIEW Passed
12/26/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2003 MONICA VALDEZ OUT TO CUSTOMER Completed