Permit Number: T02CM03201
Parcel: 140280260

Address:
2054 E GINTER RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM03201
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2002 ANY FLOODPLAIN REVIEW Approved
07/05/2002 MICHAEL ST. PAUL ZONING REVIEW Passed
08/08/2002 JIM EGAN FIRE REVIEW Denied SEE SITE COMMENTS
08/09/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide up and down stream M.H. Rim Elev., slope of sewer, water meter and water lines, size on 400-C1.1. 2.Condensate lines shall be taken to the P-6's or if the P-6's are not used the condensate shall be taken to the P-4 mop sink with an air gap. Detail 207 shall not be used. NOTE: Detail 205 indicates a 1-1/2" taken to a 1-1/4" tailpiece, nothing larger than a 1" condensate line is to be attached to a LAV tailpiece. 3. How many WH-1's ? indicate on the plan.
08/09/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Architectural drawing 4/400-A3.1 does not reflect MEC. 2. Show on the plan how trhe mechanical design complies with Chapter 4 IMC 2000.
08/09/2002 HOLLY PEARCE WATER REVIEW Denied See Plumbing comments.
09/03/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied GENERAL COMMENTS
1) Please return the plans I have already reviewed along with your next submission.
2) Provide IECC light budget calculations.
E2.1
1) The restrooms lack a circuit number. Circuit P4 on page E3.1 appears to be in error as it shows circuit 4 as the bathroom circuit. Please provide the circuit and load in the panel.
E3.1
1) 99NEC 225-36 requires the panel/disconnect serving building 400 be service entrance rated.
E0.0 and E5.1
1) 99NEC 225-30 allows 1 feeder to building 400. Provide justification for more than 1 feeder.
E5.1
1) The NEC code references for detail B are incorrect. Please revise.
2) Provide a UFER ground which is placed in the footing of each wing and connect it to the service rated panel in the electrical room. The wings are neither connected by footings or the roof structure. See 400-S1.0 and 400-S2.0.
3) Remove the ground wire from the service lateral.
E6.1
1) Provide a common ground in point (the service grounding electrode system) for the TELE/DATA, VIDEO, CLOCK, INTERCOM SYSTEM. See 99NEC-800 D. 99NEC 725-54(c).
09/26/2002 GERRY KOZIOL WWM REVIEW Approved
10/28/2002 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approv-Cond Pima County Development Services
201 N. Stone Av. 1st. Floor
Tucson Arizona 85701
Department of Building and Safety
Correction Sheet 1 of 2


ADDRESS : 2054 E GINTER RD T02CM03201
WORK : SCHOOL DATE : 9/23/02
OCCUPANCY : CONST.
ARCHITECT : PAUL D MICKELBERG PHONE : 520-408-1044
ENGINEER : STEVEN A HESS PHONE : 520-318-0004
APPLICANT : ARCHITECT



GENERAL COMMENTS

U-values for windows and doors, and shading coefficient for windows shall be indicated on the plans.

Calculations specify R-values for roof insulation to be R-30. Plans show 3" rigid insulation with a total R value of 20.

Provide a copy of the soils report. Soils report shall substantiate the site class as "C"

Total occupant load for this building is 324 occ > 250 occ. IE = 1.25 and Iw = 1.15 as per
Table 1604.5.

1704.3 Steel Construction. Special inspection is required for all field welded connections.

1704.4 Concrete Construction. Special inspection is required for concrete where design
f’c > 2500 psi.

Special inspection is required by an Arizona licensed engineer for Placement of Reinforcement for concrete to final inspection.

Table 1704.5 Masonry Construction. Special inspection is required for Structural Masonry construction.

1704.7 Earth Work. Special Inspection by an Arizona licensed engineer is required during Earth Work Grading, Excavation, Filling operations and compaction tests to satisfy requirements of the Soils Report.
Pima County Development Services
201 N. Stone Av. 1st. Floor
Tucson Arizona 85701
Department of Building and Safety
Correction Sheet 2 of 2



A SPECIAL INSPECTION CERTIFICATE, furnished by the City of Tucson is required to be completed and signed by the Owner and Engineer responsible for carrying out the required special inspections prior to obtaining a building permit. Please note that the Owner or his Legal Agent must also sign the Special Inspection Certificate.

Provide specifications for metal deck welding, shear transfer.

The installation of air conditioning and other equipment (such as compressors, fans, condensers and transformers) must be detailed on and made part of the plans

Structural plans and calculations are required for support of all roof equipment unless installed under a separate permit. The weight of roof equipment shall also be included in the seismic design.

I am available between 8:00 A.M. to 12:00 noon and 2:00 P.M. to 4:00 P.M. daily. Please feel free to call or make an appointment to discuss or clarify any of these comments.












EDWARD J. COURTNEY
520-740-6492

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2002 MONICA VALDEZ OUT TO CUSTOMER Completed