Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM02654
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/31/2002 | FRANK KALINSKI | WATER | REVIEW | Approved | |
| 06/20/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1.Architectural drawings do not reflect M.E.C. Calc's. 2. Provide outside air to the dressing rooms Per Chapter 4 IMC 2000. |
| 06/20/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide F.F.E. of building,M.H.Rim Elev., waste line size and slope on the site plan. 2. Provide a waste line isometric drawing on the plan. 3. Inclued the RPPB in the water demand calculations. 4. PVC roof drains shall comply with IAPMO IS 8-92. 5. Show all of the plumbing and roof drains on the plumbing plans. |
| 06/25/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
| 07/10/2002 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 07/17/2002 | GERRY KOZIOL | WWM | REVIEW | Denied | |
| 07/17/2002 | ANY | FLOODPLAIN | REVIEW | Approved | |
| 07/19/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 7/19/2002 Building plans will be reviewed once the structural reviewers have approved the plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/19/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |