Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY COMMERCIAL TI
Permit Number - T02CM02634
Review Name: 3RD PARTY COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 05/29/2002 | FRANK KALINSKI | WATER | REVIEW | Approved | |
| 05/29/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/09/2002 | DAN CASTRO | NPPO | REVIEW | Passed | |
| 07/09/2002 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
| 07/11/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/11/2002 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |