Permit Number: T02CM02009
Parcel: 117032670

Address:
700 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T02CM02009
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2003 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved
01/22/2003 PETER MCLAUGHLIN ZONING REVIEW Denied TO: The IEF Group, Inc.
705 N. Seventh Ave
Tucson, AZ 85705

FROM: Peter McLaughlin
Senior Planner
FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T02CM02009
The IEF Group, Inc.
Architects/Planners
700 N. Stone Ave.
Site Plan Review (2nd review)

TRANSMITTAL: January 22, 2003

Upon completion of the following revision/addition, an over the counter review may be arranged to obtain stamped approval by the zoning review section without resubmitting the site plan. The following item must be revised on or added to the site plan:

1. If sheet G 1.0 is going to remain as the "Title Sheet", revise legal description to be correct, revise on and off-site parking layout, remove all notes/references to nonconforming status, and make all other applicable changes per first review comments. Otherwise, remove sheet G 1.0 and place legend, sheet index , etc. on variance site plan sheet G 1.1.
DS 2-02

2. Add the Board of Adjustment variance case number, date of approval, what the variances were approved for and any conditions of approval on the site plan.
DS 2-02.2.1.A.38

3. Revise setback note on drawing and in the calculation notes to specify that the required MS&R street perimeter yard setback is 22 feet, which is the height of exterior building wall, measured from back of future curb location.
LUC 3.2.6.5

4. The near side sight visibility triangles, at the intersection of Stone Ave and 4th St. (dimensioned at 340'), and at the intersection of Echols Ave and 4th St. (dimensioned at 110'), are drawn incorrectly and may be removed since they do not impact the project site.
DS 2-02.2.1.A.10

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
01/24/2003 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Indicate lot bearings along with dimensions of site. D.S. 2-02.2.1.5

2. Indicate a downspout and roof drain detail. Indicate roof drainage discharge on north side of building how it impacts adjacent property. D.S. 2-02.2.1.6

3. Indicate if existing sidewalk scupper meets development standard details D204 or D205.

4. Label existing and future sight visibility triangles. D.S. 2-02.2.1.10

5. Indicate refuse container location, size and access thereto fully dimensioned. Screening and gates are required for refuse enclosure. If existing conditions are to remain, a signature from Rene Duarte of Solid Waste is required.
D.S. 2-02.2.1.32 Indicate a refuse enclosure detail. D.S. 6-01.4.2.A-D
01/28/2003 BLANCA ESPINO FLOODPLAIN REVIEW Denied SEE ENGINEERING COMMENTS.
01/28/2003 BLANCA ESPINO SANITATION REVIEW Denied SEE ENGINEERING COMMENTS.
01/31/2003 JOE LINVILLE LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2003 MONICA VALDEZ OUT TO CUSTOMER Completed