Permit Number: T02CM01345
Parcel: 125121110

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM01345
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2002 PATRICIA GEHLEN ZONING REVIEW Approved
03/12/2002 BLANCA ESPINO FLOODPLAIN REVIEW Approved
03/13/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved SEE COMMENTS ON APPLICATION.
03/13/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
03/13/2002 JIM EGAN FIRE REVIEW Approved
03/13/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
03/13/2002 MARK TITUS WATER REVIEW Approved
03/22/2002 GERRY KOZIOL WWM REVIEW Approved
03/22/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved 1) Reduce circuit breaker sizes for circuits AA-12,14,16 and BB-20,22,24 to 70 amp or increase the conductor size to #4 copper. 99NEC 310-16 and 240-6.
2) Panel AA has 3 kitchen loads (4 if you include the WH) thus a maximum of .8 demand may be applied. The result is that panel AA is overloaded, 106 amps high phase, 103 amp average. 99NEC 220-20

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2002 MONICA VALDEZ OUT TO CUSTOMER Completed