Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM01345
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 03/12/2002 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved | |
| 03/13/2002 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | SEE COMMENTS ON APPLICATION. |
| 03/13/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/13/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/13/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/13/2002 | MARK TITUS | WATER | REVIEW | Approved | |
| 03/22/2002 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/22/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1) Reduce circuit breaker sizes for circuits AA-12,14,16 and BB-20,22,24 to 70 amp or increase the conductor size to #4 copper. 99NEC 310-16 and 240-6. 2) Panel AA has 3 kitchen loads (4 if you include the WH) thus a maximum of .8 demand may be applied. The result is that panel AA is overloaded, 106 amps high phase, 103 amp average. 99NEC 220-20 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/22/2002 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |