Permit Number: T02CM01092
Parcel: 11614163A

Address:
2010 W ANKLAM RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM01092
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2002 JIM EGAN FIRE REVIEW Approved
05/30/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied
05/30/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved
05/30/2002 GERRY KOZIOL WWM REVIEW Approved
05/30/2002 DAVID RIVERA ZONING REVIEW Approved
05/30/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
05/30/2002 FRANK KALINSKI WATER REVIEW Approved
05/30/2002 ANY FLOODPLAIN REVIEW Approved
06/03/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-1 and 2
1) Provide a #10 copper conductor for the dryer, circuit B1-39/41
2) Circuit B2 19,21,23 serving the hot water tank must be a minimum 35 amp. See 99NEC 422-13 and 240-3. Revise keynote #5 page E-2
3) It appears one of the PT floor receptacles should be circuited to B1-35/37.
4) Circuits B1-20,22,24 appear in the panel schedule however I could not find them on the plan.
5) It appears the electrical installation is required to be in compliance with 99NEC 517-13. The specifications should not permit PVC conduit, in addition they should require metallic conduit systems throughout and include an insulated green equipment grounding conductor. See 99NEC 517-13.
6) Provide an IECC light budget calculation. In addition provide dual switching throughout the PT area. This facility is allowed 1.8W/ft2.

Please return the plans I have already reviewed along with the next submittal. Please use a cloud and delta format to distinguish the changes made to the second submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2002 LISA LESNY OUT TO CUSTOMER Completed