Permit Number: T02CM01019
Parcel: 12620001A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T02CM01019
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2003 EROSE1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed City of Tucson No. T02CM01019-R

GENERAL:

q There is a reference on Sheet E1.00 regarding a structural light pole base detail for light pole bases that are a part of a retaining wall. Please provide for review and approval the "sketch" that is referenced on this sheet. It is possible that this sketch was already submitted and approved under an earlier revision and there simply is not a copy in the approved reference set we have. If so, then please provide an approved copy of this "sketch".

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q There are no structural comments to be addressed.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q The waste line on Sheet P2.1.2 has been revised. The main waste line parallel and adjacent to Grid Line "D" changes from 4" to 6" at some point. Please clarify where does this change need to take place. Also, the notes on this page indicate that the 6" pipe reduces back to a 4" pipe? There are two notes that still indicate a 4" dia. pipe when they should have been changed to 6" dia. pipes.

q There is a revised note on Sheet P2.2.2 that indicates to reference Sheet P1.1.1 for continuation of the sanitary waste pipe. This appears to be incorrect (There is no P1.1.1 in the originally approved set or listed in the drawing index). The reference should be P2.1.2. Please coordinate.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-
04/04/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied City of Tucson No. T02CM01019-R

GENERAL:

q There is a reference on Sheet E1.00 regarding a structural light pole base detail for light pole bases that are a part of a retaining wall. Please provide for review and approval the "sketch" that is referenced on this sheet. It is possible that this sketch was already submitted and approved under an earlier revision and there simply is not a copy in the approved reference set we have. If so, then please provide an approved copy of this "sketch".

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q There are no structural comments to be addressed.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q The waste line on Sheet P2.1.2 has been revised. The main waste line parallel and adjacent to Grid Line "D" changes from 4" to 6" at some point. Please clarify where does this change need to take place. Also, the notes on this page indicate that the 6" pipe reduces back to a 4" pipe? There are two notes that still indicate a 4" dia. pipe when they should have been changed to 6" dia. pipes.

q There is a revised note on Sheet P2.2.2 that indicates to reference Sheet P1.1.1 for continuation of the sanitary waste pipe. This appears to be incorrect (There is no P1.1.1 in the originally approved set or listed in the drawing index). The reference should be P2.1.2. Please coordinate.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2003 ELAINE ROSE OUT TO CUSTOMER Completed