Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T01EL02420
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/26/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1) The design indicates a 4 pole transfer switch, thus you have established a separately derived system. Provide a grounding electrode system at the gutter/disconnect location. See 99NEC 250-30 2) Provide a 24W x 24L x 8D pull box for feeder to LPP1. See 99NEC 370-28(a). 3) Provide a fault current analysis from the generator to panels served by the generator. Include the component short circuit current rating of the panels. |