Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01EL02420
Parcel: 13216600B

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T01EL02420
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved 1) The design indicates a 4 pole transfer switch, thus you have established a separately derived system. Provide a grounding electrode system at the gutter/disconnect location. See 99NEC 250-30
2) Provide a 24W x 24L x 8D pull box for feeder to LPP1. See 99NEC 370-28(a).
3) Provide a fault current analysis from the generator to panels served by the generator. Include the component short circuit current rating of the panels.