Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T01CM04824
Parcel: 140430130

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM04824
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2001 PETER MCLAUGHLIN ZONING REVIEW Passed
10/01/2001 JIM EGAN FIRE REVIEW Approved
10/01/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Passed
10/01/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
10/01/2001 BLANCA ESPINO FLOODPLAIN REVIEW Approved
10/17/2001 TOM CLARK WATER REVIEW Approved
10/17/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION.
10/23/2001 CAGUILAR WWM REVIEW Passed
10/23/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.DP 2,4,6 contradicted on panel schedule, its used as 75 kva transformer feed but on sheet 16 DP 2,4,6 are used for a heat pump feeder.
2.Circuits B 1,3,5,7,9,11 should be using 3 pole breakers not single pole.
3.Circuits A 1,3,5,7,9,11 appear to be under calculated.Please provide the ballast load so I can verify these loads are correct.(please double check your calculations).
4.Provide fixture cut sheets on all outdoor fixtures.
5.Install grounding electrode system at new building and bond metalic piping systemsas required.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2001 JKOZUCH OUT TO CUSTOMER Completed