Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM03417
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/11/2001 | TOM WEIDEMAN | FLOODPLAIN | REVIEW | Approved | |
| 07/11/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/11/2001 | MARK TITUS | WATER | REVIEW | Approved | |
| 07/27/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | E-1 1) It appears the conduit size for circuit "102"-1,3,5 is incorrect. E-2 1) Provide a minimum #10 equipment-grounding conductor in the 30 amp feeder circuits serving the 3-ton A/C's. See 99NEC 250-122 2) The A/C loads in the panel schedules appear low. Please provide nameplate load data. Revise panel loads, service loads, and circuit design as necessary. 3) One of the 3 ton A/C's is connected to a 20 amp CB while the other is connected to a 30 amp CB. Please clarify. 4) The conductor size for the 5-ton A/C unit appears incorrect and the load in the panel appears to be too small. 5) Remove the reference to circuit 2,4,6 under the 3 ton A/C adjacent to the bathrooms. 6) Each four-plex receptacle must be calculated as a minimum of 360VA. 99NEC 220-3(b)(9) 7) The evaporative cooler in suite 107 appears to be connected to the wrong circuit and panel. 8) Keynote number 8 is pointed to what appears to be panel 102. This is in conflict with the keynote legend. 9) Provide the termination can ampacity for the service. 10) Provide a fault current analysis for the new panel. As an option a fully listed and labeled short circuit series rated system giving the panel a 75,100 amp withstand rating may be specified. See 99NEC 90-7, 110-3(a)(b), 110-9, 110-10, 110-22, and 240-86(a)(b). 11) The suite number should be 103 not 102 as shown. Please revise as necessary. Revise both E-1 and E-2. 12) See red line set of blue-line submittal. |
| 07/30/2001 | MVALDEZ | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/30/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 07/30/2001 | MVALDEZ | WWM | REVIEW | Passed | |
| 07/30/2001 | MVALDEZ | MECHANICAL-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/30/2001 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |