Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM02400
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/18/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
05/18/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
05/18/2001 | DAVID RIVERA | ZONING | REVIEW | Approved | |
05/21/2001 | BOB SUBA | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/21/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | S1) SHOW PUBLIC TOILET ROOMS AND DIMENSION FROM PROJECT SPACE. ............................................................................ S2) PROVIDE STRUCTURAL CALCULATIONS AND DETAILS, INCLUDING FASTENER ( TYPE , SIZE , SPACING /NUMBER) FOR SUPPORT OF STOREFRONT 21/A3, 7/A5, 19/A5, 17/A6, 24/A6, /4/M2, 5/M2 AND SHELVING OVER (8) EIGHT FEET HIGH. .................................................................................................. S3) FULLY DETAIL ACCESSIBLE TOILET ROOM 19/A3 ............ S4) PROVIDE NOTE ON EXIT DOOR " THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.".............. |
05/21/2001 | BOB SUBA | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/27/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.provide breaker for 30 kva transformer. 2.calculate track lighting per N.E.C. 220-12b 3.calculate cir. A-11 correctly 4.recalculate loads at panels H&A 5.provide names and loads of existing tenants 6.panel A should indicate having a main breaker@ panel schedule 7.indicate the S.E.S. name and location |
06/29/2001 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/29/2001 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |