Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
06/21/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved 1) Original write up from May 18,2001 . Each tenant must include the following information about the mall service:Service location,service name,total service capacity,total service load (both new and existing),available fault current at the line terminals of the service,total number of service disconnects,the type and size of over current device protecting the feeder conductors to tenant, and a complete one line service diagram .

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2001 LISA LESNY OUT TO CUSTOMER Completed
06/21/2001 LISA LESNY APPROVAL SHELF Completed