Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T01CM02368
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/21/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1) Original write up from May 18,2001 . Each tenant must include the following information about the mall service:Service location,service name,total service capacity,total service load (both new and existing),available fault current at the line terminals of the service,total number of service disconnects,the type and size of over current device protecting the feeder conductors to tenant, and a complete one line service diagram . |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/25/2001 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 06/21/2001 | LISA LESNY | APPROVAL SHELF | Completed |