Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/04/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
05/08/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
05/09/2001 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
05/16/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1. circuits CL2-21,23,25,27,29,32,34,36 need to be calculated at 150 voltamperes per 220-12b 1999 N.E.C.,recalculate loads to reflect 220-12b. 2. At Detail 4 on sheet E-2 indicate what type of bushing your asking for. 3.Provide an equip. grounding conductor between the underfloor duct and the equipment served . 4.Calculate each receptacle at a min. of 180 voltamperes and each quadplex at 360 voltamperes. 5.Install an equipment grounding conductor through all flex. conduit per local ammendments to the 1999 N.E.C. . 6. Indicate all motor overcurrent protection per Art. 430 -C 1999 N.E.C. |
05/22/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/22/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
06/01/2001 | JKOZUCH | WWM | REVIEW | Approved | |
06/08/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/15/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |