Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM02163
Parcel: 137335720

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM02163
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
05/08/2001 JIM EGAN FIRE REVIEW Approved
05/09/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
05/16/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved 1. circuits CL2-21,23,25,27,29,32,34,36 need to be calculated at 150 voltamperes per 220-12b 1999 N.E.C.,recalculate loads to reflect 220-12b.
2. At Detail 4 on sheet E-2 indicate what type of bushing your asking for.
3.Provide an equip. grounding conductor between the underfloor duct and the equipment served .
4.Calculate each receptacle at a min. of 180 voltamperes and each quadplex at 360 voltamperes.
5.Install an equipment grounding conductor through all flex. conduit per local ammendments to the 1999 N.E.C. .
6. Indicate all motor overcurrent protection per Art. 430 -C 1999 N.E.C.
05/22/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
05/22/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Passed
06/01/2001 JKOZUCH WWM REVIEW Approved
06/08/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2001 SUE REEVES OUT TO CUSTOMER Completed