Review Details: REVISION

Permit Number - T01CM02145
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Ccondensate lines shall discharge into an approved plumbing fixture, ie: Floor sink- Mop sink.
05/30/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1-0.2
1) Loads for EM1A have been revised as a result of a load modification to EM1C circuit 6 on page E2-0.2 however nothing in the plan demonstrates what changes were made. Please clarify.
2) EM1A indicates it is served from MSB1 however there is not a circuit shown in MSB1. Please clarify.
E2-1.25
1) Provide a floor plan depicting the location of MCC4A, disconnects, transfer switch, UPS, transformer, and UPS4L.
2) Provide T4U grounding electrode conductor size.
3) Clarify how the 30 amp disconnect and maintenance bypass switches are connected to MCC4A. If it is your intention to tap the buss as indicated in Note 4 on the plan, provide a design demonstrating exactly how the taps are to be made. The 99NEC 240-21(b)(1)(d) requires a minimum #6 copper tap conductor. Additionally a statement under the electrical engineers seal must certify the modified equipment or a new certification from an approved testing lab would be required. See 99NEC 90-7, 110-3, 110-26 and 240-21.
06/19/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON APPLICATION