Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM01124
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Denied | |
| 03/07/2001 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | |
| 03/09/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/12/2001 | TOM CLARK | WATER | REVIEW | Approv-Cond | |
| 03/13/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/13/2001 | BOB SUBA | MECHANICAL-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES MECHANICAL REVIEW COMMENTS DATE: March 13, 2001 ACTIVITY NUMBER:T01CM01124 PROJECT- SCHOOL PROJECT ADDRESS: 1200 N.SANTA ROSA PROJECT REVIEWER: Robert Suba (1) Water heater venting shall comply with sec. 806.4 1994 Uniform Mechanical Code (2) Indicate on plans how you will be in compliance with sec. 703.7 1994 Uniform Mechanical Code at the janitors closet (3) Exhaust grill in janitors closet is attached to the supply air duct. Is this supposed to be connected to the exhaust duct ? If so, please indicate on the plans showing it connected to the appropriate duct. |
| 03/14/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/27/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 03/29/2001 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/12/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |