Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM00086
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/05/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/05/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/05/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 01/05/2001 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/05/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/17/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | E-3 1) Provide the location of the junction box that intercepts the feeder on the load side of the service disconnect. The tap from the JB to the existing 125amp panel cannot exceed 25'. The tap from the JB to the line side of the transformer, extending through the transformer, and including the secondary conductors cannot exceed 25' total length. See 99NEC 240-21 for various tap requirements. 2) Provide the building service size, capacity, and final load including the new loads for this space. |
| 01/22/2001 | RAY MORGAN | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/09/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/09/2001 | DELMA ROBEY | REJECT SHELF | Completed |