Review Details: COMMERCIAL TI

Permit Number - T01CM00086
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2001 JIM EGAN FIRE REVIEW Approved
01/05/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
01/05/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/05/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
01/05/2001 DAVID RIVERA ZONING REVIEW Approved
01/05/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
01/17/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved E-3
1) Provide the location of the junction box that intercepts the feeder on the load side of the service disconnect. The tap from the JB to the existing 125amp panel cannot exceed 25'. The tap from the JB to the line side of the transformer, extending through the transformer, and including the secondary conductors cannot exceed 25' total length. See 99NEC 240-21 for various tap requirements.
2) Provide the building service size, capacity, and final load including the new loads for this space.
01/22/2001 RAY MORGAN WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2001 DELMA ROBEY OUT TO CUSTOMER Completed
02/09/2001 DELMA ROBEY REJECT SHELF Completed