Permit Number: T01CM00053
Parcel: 113040020

Address:
1302 E PRINCE RD

Review Status: Completed

Review Details: SITE

Permit Number - T01CM00053
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2001 DAN CASTRO ZONING REVIEW Denied
01/24/2001 JIM EGAN FIRE REVIEW Approved
01/24/2001 JOE LINVILLE NPPO REVIEW Denied
01/24/2001 JLINVILL LANDSCAPE REVIEW Denied
02/26/2001 JIM JOHNSEN FLOODPLAIN REVIEW Denied See Engineering comments
02/26/2001 JIM JOHNSEN ENGINEERING REVIEW Denied 1. The next submittal of the site plan must be accompanied by a Hydrology Report prepared, sealed, and signed by an Arizona registered professional civil engineer. Such report should be prepared in accordance with the Standards Manual for Drainage Design and Floodplain Management in Tucson, Arizona and address, at a minimum, offsite flow acceptance, existing and proposed peak stormwater discharge, and a floodplain analysis for the adjacent Mountain Avenue Wash under existing and proposed conditions. If the increase in runoff will adversely impact the Mountain Avenue Wash and properties and structures adjacent to the wash, 5-year threshold retention will need to be provided with respect to the proposed development. (Development Standard 2-02.2.2.C)
2. Dimensions and bearings should be provided for the lot on the site plan (sheet A-1). A basis of bearing should also be provided on the site plan. (Dev. Std. 2-02.2.1.A.5)
3. Existing and future sight visibility triangles (SVT's) for the parking lot drive adjacent to the proposed development should be shown with the lengths of each annotated on the plan. (Development Standard 2-02.2.1.A.10)
4. The width of all existing and proposed parking area access lanes (PAALs) in the proposed development should be shown. (Dev. Std. 2-02.2.1.A.11)
5. Limits of the 100-year floodplain and associated water surface elevations for the Mountain Avenue Wash floodplain should be shown. (Dev. Std. 2-02.2.1.A.15)
6. Existing and proposed site drainage patterns, proposed finished floor elevations, and finish site grades for the new development should be shown. (Dev. Std. 2-02.2.1.A.16)
7. Estimated cut and fill quantities should be shown on the site plan for the purpose of determining grading permit requirements. (Dev. Std. 2-02.2.1.A.17)
8. Existing and future MS&R right-of-way dimensions for Prince Road, Mountain Avenue, and Greenlee Road should be shown. (Dev. Std. 2-02.2.1.A.19)
9. Dimensions from the street monument line of Mountain Avenue to the existing edge of pavement and to the future MS&R face of curb should be shown. The future MS&R face of curb will be 9-feet from the future MS&R right-of-way for Mountain Avenue. Please show and label existing curb, if applicable. (Dev. Std. 2-02.2.1.A.21)
10. The existing Mountain Avenue Wash and the existing culverts beneath the site driveways should be shown and labeled on the site plan. (Dev. Std. 2-02.2.1.A.22)
11. Existing topographic contours at intervals not exceeding 2-feet and/or spot elevations and the bench mark used for vertical information based on City of Tucson datum, including city field book and page number, should be provided on the site plan. (Dev. Std. 2-02.2.1.A.23)
12. If any walls are proposed and/or existing, the location, type, material, and openings for stormwater runoff acceptance and/or discharge should be shown. (Dev. Std. 2-02.2.1.A.27)
13. The existing dumpster should be enclosed per Development Standard 6-01. (Dev. Std. 2-02.2.1.A.32)
02/26/2001 PHIL SEADER HANDICAP-SITE REVIEW Denied
02/26/2001 JIM JOHNSEN SANITATION REVIEW Denied See Engineering comments

Final Status

Task End Date Reviewer's Name Type of Review Description
03/15/2001 MVALDEZ OUT TO CUSTOMER Completed