Permit Number: T00EL02437
Parcel: 117180860

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T00EL02437
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2000 ANY ELECTRICAL-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
ELECTRICAL REVIEW COMMENTS

DATE: October 24, 2000
ACTIVITY NUMBER: T00EL02437
PROJECT NAME: Apartment Rewire
PROJECT ADDRESS: 400 S. El Paso #01
PROJECT REVIEWER: Randy Schuler, P.E.
Page 1 of 2
SECOND REVIEW
APARTMENTS A, B, C
3) Describe the exterior lights. COT light ordinance.
NEW. Indicate an incandescent light source.
4) Provide a typical panel schedule. Include bracing, N3R rating, breaker
sizes, and number of circuits.
NEW. Provide bracing and N3R rating.
APARTMENT A ONLY
1) A pull chain fixture cannot mount in the clothes closet. 99NEC 410-8(c).
NEW. Indicate fluorescent lighting.
2) Describe the light fixtures within the closets, see 99NEC 410-8(b).
NEW. Indicate fluorescent lighting.

APARTMENTS B AND C ONLY
2) Provide a minimum of (2) 20 amp GFCI circuits above the kitchen
counter. 99NEC 210-11(c)(1) and 210-8(a)(6).
NEW. Provide a receptacle on the other side of the sink in unit C on circuit C2.

NEW COMMENTS AS A RESULT OF THE SECOND REVIEW.
1) Provide a separate circuit for the cooler in bedroom #2 of unit A.
2) Please remove all of the correction numbers from the plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2000 CLAUDIA BUFORD APPROVAL SHELF Passed
10/27/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
10/27/2000 CLAUDIA BUFORD REJECT SHELF Passed