Permit Number - T00EL02437
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2000 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES ELECTRICAL REVIEW COMMENTS DATE: October 24, 2000 ACTIVITY NUMBER: T00EL02437 PROJECT NAME: Apartment Rewire PROJECT ADDRESS: 400 S. El Paso #01 PROJECT REVIEWER: Randy Schuler, P.E. Page 1 of 2 SECOND REVIEW APARTMENTS A, B, C 3) Describe the exterior lights. COT light ordinance. NEW. Indicate an incandescent light source. 4) Provide a typical panel schedule. Include bracing, N3R rating, breaker sizes, and number of circuits. NEW. Provide bracing and N3R rating. APARTMENT A ONLY 1) A pull chain fixture cannot mount in the clothes closet. 99NEC 410-8(c). NEW. Indicate fluorescent lighting. 2) Describe the light fixtures within the closets, see 99NEC 410-8(b). NEW. Indicate fluorescent lighting. APARTMENTS B AND C ONLY 2) Provide a minimum of (2) 20 amp GFCI circuits above the kitchen counter. 99NEC 210-11(c)(1) and 210-8(a)(6). NEW. Provide a receptacle on the other side of the sink in unit C on circuit C2. NEW COMMENTS AS A RESULT OF THE SECOND REVIEW. 1) Provide a separate circuit for the cooler in bedroom #2 of unit A. 2) Please remove all of the correction numbers from the plan. |