Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T00CM05561
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | DENIED 10/28/03 T00CM05561 GND run in feeders to Panels A & B shall be #4 per NEC Table 250-66. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |