Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T00CM05561
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/11/2002 | MARK TITUS | WATER | REVIEW | Approved | |
| 02/11/2002 | JAMES TATE | FLOODPLAIN | REVIEW | Denied | |
| 02/11/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | |
| 02/25/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/25/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide the up stream M.H. Rim Elev. on the site plan. Show on the site plan where the sewer line comes out of the building and attaches to the HCS and the slope of same. If the FFE is not one foot higher than the up stream M.H. Rim provide a back water valve and access to same. Provide an access detail on the site plan. 2. Redo the water demand calculations. Water pressure can not exceed 80 PSI. Sec608.2 UPC 1994 Az. Code, inclued RP assem. in the water demand calc's. |
| 02/25/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Provide access to the elevated roof ( sec4/6 on sheet 8) Per Sec 306.5 IMC 2000. 2. Complete OSA calculations Per Chapter 4 IMC 2000. |
| 03/04/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 03/07/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/08/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |